. ® PROGRAMMABLE CONTROLLER User’s Manual FP0 User’s Manual ARCT1F389E-2 ’07.06 Matsushita Electric Works, Ltd. Safety Precautions Observe the following notices to ensure personal safety or to prevent accidents. To ensure that you use this product correctly, read this User’s Manual thoroughly before use. Make sure that you fully understand the product and information on safe.
- You may not copy this manual,in whole or part,without written consent of Panasonic. 1.1.1 FP0 Control.
- Factory Automation Devices: Programmable Logic Controllers (PLC) Panasonic PLCs offer an. Panasonic's PLC programming software, Control FPWIN Pro.
This manual uses two safety flags to indicate different levels of danger. Introduction Introduction This manual explains hardware configurations, installation, wiring procedures, I/O allocations and maintenance. Power supplies An insulated power supply with an internal protective circuit should be used. The power supply for the FP0 control unit operation is a non-insulated circuit, so if an incorrect voltage is directly applied, the internal circuit may be damaged or destroyed. Before You Start Power supply sequence Have the power supply sequence such that the power supply of the FP0 control unit turns OFF before the power supply for I/O. If the power supply for I/O is turned OFF before the.
Panasonic User Manuals Operating Installation. In 1974 Panasonic Electric Works. Control FPWIN Pro FP0/FP1/FP-M PLC Programming Manual: 3.
Programming manual Manual No. No.ARCT1F389E No.ARCT1F313E FP0 Control unit FP0 Expansion unit FP0 Thermocouple unit ARCT1F366E FP0 Analog I/O unit ARCT1F390E FP0 A/D conversion unit ARCT1F321E FP0 D/A conversion unit ARCT1F382E FP0 CC−Link slave unit ARCT1F380E FP0 I/O link unit FP0 Power supply unit −. 1.1.1 FP0 Control Units. Table of Contents 2.3.2.2 PNP Open Collector Type (C16P/C16CP/C32P/C32CP/T32CP). 2 − 21 Pin Layouts.6 − 8 Installation Using FP0 Slim Type Mounting Plate.
Table of Contents 7.1.1 Interlock Circuit. Table of Contents 8.5.2 Operation and Precautions at Run Start Time.8 − 14 8.5.3 Precautions When Using a Control Instruction.8 −. 12 − 14 12.5.1 FP0 Power Supply Unit (AFP0634). 12 − 14 12.5.2.14 - 17 14.1.2 Table of Special Internal Relays for FP0.14 - 20 14.1.3.
Table of Contents.1 − 3 1.1.1 FP0 Control Units. Overview 1 − 2. Overview Components Components 1.1.1 FP0 Control Units Specifications Built−in Built−in Product memory Product Power Part No. Number of Connection name (Program supply Input Output I/O points type capacuty) voltage 24 V DC EEPROM Input: 6 24 V DC Relay out- Terminal block FP0−C10RS. Overview Components 1.1.2 FP0 Expansion Units Specifications Product Power Part No. Number of Connection name supply Input Output I/O points type voltage 24 V DC Input: 8 — — MIL connector FP0−E8X AFP03003 Sink/Sourse ( common) 24 V DC. 24 V DC FP0−CCLS AFP07943 FP0 CC− Only one unit can be connected to the furthest right edge of the FP0 expansion bus.
Link Slave Note: Accuracy will change if an FP0 thermocouple unit is used at the same time. Unit For details, please refer to the catalog or to the CC−Link Unit manual. (2 sockets per pack) Attaches to transistor output type. Additional part AFP0807 Wire−press socket (2 sockets per pack) Attaches to FP0 various units. Additional part Length: 1 m/3.281 ft.
AFP0581 FP0 Power cable (1 socket per pack) 1 − 6. Overview 1.2 Expansion Possibilities Expansion Possibilities Be sure to check that the units are added according to the following restrictions: A maximum of three expansion I/O units or analog I/O units can be connected to one control unit. There are no restrictions on the combinations of the kind control units and expansion units.
Panasonic Plc Manual
Overview Combination Possibilities Combination Possibilities 1.3.1 Relay Output Type Units First Second Third Total number of Control expansion expansion expansion I/O points unit I/O unit I/O unit I/O unit Input: 6 Output: 4 Input: 6 Output: 4 Input: 8 Output: 6 Input: 8 Output: 6 Input: 10. Overview Combination Possibilities 1.3.2 Transistor Output Type Units First Second Third Total number of Control expansion expansion expansion I/O points unit I/O unit I/O unit I/O unit Input: 8 Output: 8 Input: 8 Output: 8 Input: 16 Output: 16 Input: 16 Output: 16 Input: 8 Output: 8. GR Ver.2” after purchasing the upgraded version software. (The upgrade version software can be installed only when the “Ver.1.1” has been previously installed) 2) Small type version can be used for the “FP−e,” “FPΣ,” “FP0,” “FP−X,” “FP1,” and “FP−M” series. IEC61131−3−compliant programming tool software FPWIN Pro Ver.5. Chapter 2 Control Units Parts and Terminology.2 − 3 2.1.1 Control Unit Types.
Optional Memory Pin Layouts.2 − 22 2.4.1 C10RS/C10CRS/C10RM/C10CRM. Optional Memory Parts and Terminology Parts and Terminology There are sixteen different control unit types available: C10RS terminal type C14RS terminal type C10CRS (with RS232C port) terminal type C14CRS (with RS232C port) terminal type C10RM connector type C14RM connector type C10CRM (with RS232C port) connector type C14CRM (with RS232C port) connector type C16T. Optional Memory Parts and Terminology 2.1.1 Control Unit Types C10RS/C14RS C10RM/C14RM All control unit types C10CRS/C14CRS C10CRM/C14CRM (terminal type) (connector type) EXPANSION CONNECTOR C16T/C16CT C32T/C32CT Control unit with RS232C port C16P/C16CP C32P/C32CP T32CT/T32CP 2 − 4. ) (.section 7.7).
Expansion hook 13 16 is used to secure expansion units. The hook is also used for installation on FP0 flat type mounting plate (AFP0804). Expansion connector connects an expansion unit to the internal circuit of the control unit (.section 6.1). Mode Switch 2.1.1.2 This switch turns ON and OFF (RUN/PROG.) the operation of the FP0.
The FP0 can also be turned ON and OFF by the programming tool. Switch position Operation mode RUN (upward) This sets the RUN mode. Optional Memory Specifications Specifications 2.2.1 General Specifications Item Description Rated operating voltage 24 V DC Operating voltage range 21.6 V to 26.4 V DC (.section 2.2.1.2 Rated current consumption 300 mA or less Allowed momen- C10/C14 5 ms at 21.6 V, 10 ms at 24 V tary power off time ff ti C16/C32. ) FP0 Control unit FP0−C10 100mA or less — 25.8mA or less — FP0−C14 100mA or less — 34.4mA or less — FP0−C16 40mA or less —. Optional Memory Specifications Current consumption example C14RS E32T E16T E16RS At power supply connector of expansion I/O unit FP0 E16RS Type Current consumption FP0 E16RS 100 mA At power supply connector of control unit Type Current consumption FP0 C14RS 100 mA.
Optional Memory Specifications 2.2.2 Performance Specifications Item Relay output type Transistor output type S−LINK type C10RS/ C14RS/ C16T/ C32T/ T32C C10RM/ C14RM/ C16P/ C32P/ C10CRS/ C14CRS/ C16CT/ C32CT/ C10CRM C14CRM C16CP C32CP Programming method/Control method Relay symbol/Cyclic operation Controllable I/O Total: 32 Basic unit Total: 10. Optional Memory Specifications Item Relay output type Transistor output type S−LINK type C10RS/ C14RS/ C16T/ C32T/ T32C C10RM/ C14RM/ C16P/ C32P/ C10CRS/ C14CRS/ C16CT/ C32CT/ C10CRM C14CRM C16CP C32CP Number of step ladders 128 stages 704 stages 128 stages (. Note 1) Number of subroutines 16 subroutines 100 sub. Optional Memory Specifications Relay output type Transistor output type S−LINK Item type C10RS/ C14RS/ C16T/ C32T/ T32C C10RM/ C14RM/ C16P/ C32P/ C10CRS/ C14CRS/ C16CT/ C32CT/ C10CRM C14CRM C16CP C32CP Special Pulse Output point Not available Two independent points (Y0 and functions u c o s output. (F168) is executed.
11) Precautions when using the battery backup function Secondary (chargeable) battery is used as backup battery in the FP0 T32C control unit. The battery is not charged before the unit is shipped, so please make sure that the built−in backup battery have been charged before using the unit.
Optional Memory Specifications 2.2.3 Input Specifications Item Description Insulation method optical coupler Rated input voltage 24 V DC Rated input current approx. 4.3 mA (at 24 V DC) Input impedance approx.
5.6 kΩ Operating voltage range 21.6 to 26.4 V DC Input points per C10RM, 6 points/common. Limitations on Number of Simultaneous Input ON Points Keep the number of input points per common which are simultaneously ON within the following range as determined by the temperature.
FP0-C14RM/C14CRM/C14RS/C14CRS at 24 V DC Number of at 26.4 V DC.
The Panasonic product portfolio comprises both low-cost compact programmable controllers with little space requirement which are suitable for many basic tasks and high-end PLCs like the flagship FP7. A multitude of useful functions has been successfully integrated into the compact PLCs so that they offer many of the advantages of a modular high-end PLC such as analog control, network communication, and positioning control. All Panasonic PLCs offer an outstanding price-performance ratio. Thanks to the innovative programming software Control FPWIN Pro, it takes minimal effort to achieve a maximum result with the programmable controllers. For example, the programming software provides many ready-made functions and function blocks.
This allows you to use our know-how for your programs, saving you a lot of time for programming and debugging. Like all other Panasonic products, programmable controllers are subjected to much more severe conditions than they will ever encounter in actual operation to ensure a long service life in your application. Panasonic not only offers a comprehensive PLC product range but also takes pride in providing top-notch service. For a customer-oriented company certified according to ISO 9001, such commitment is self-evident. Highly trained application engineers put together systems tailored to our customers' needs. Compact size with room for expansion functions.
Equipped with a cassette interface. Add-on cassettes can be added to the CPU to increase functionality without increasing the footprint of the system. Standard Ethernet interface with MEWTOCOL (client/server) or Modbus TCP (client/server) protocol, EtherNet/IP; up to 272 connections can be active at the same time. Available functions: SMTP, FTP client/server, HTTP client, e-mails, integrated web server. Up to 64 different units can be connected to a single CPU.
High-capacity SD (SDHC) memory cards of up to 32GB are supported. High performance (max. 20μs for 60k steps); the processing speed is less affected by frequent Ethernet communication. Software tools. PLC Programming Software according to IEC61131-3.
Standardized connectivity to FP Series PLCs. Software tool to read and display PLC data. Data monitoring, logging and setting software based on Microsoft Excel.
Connecting your application to Panasonic PLCs using ActiveX® technology. FP Web Designer, an easy-to-use editing tool helps users create websites for visualizing process data collected by the FP Web-Server. FPGT Loader The FPGT Loader allows you to upload complete programs easily to GT touch panels or FP-Series PLCs without requiring a programming system.